Technical Conquer · Free practical tool

Psychrometric calculator

Read a service air state before deciding whether a comfort complaint concerns temperature, moisture or both. Compare the dry-bulb reading with humidity ratio rather than treating relative humidity as a fixed water content.

Free results and workingNo signupLocal calculations
Your inputsCalculated on your device

Example values loaded. Replace them with your own measurements.

Your result
↗

Make the numbers make sense.

Enter your values, choose the units, and calculate. You’ll see the result and the working here.

Free results. No account needed.

The method

Water vapour pressure = RH × saturation pressure; W = 0.621945 pv/(p−pv). Wet bulb and dew point use standard psychrometric relationships.

Before using the result

  • Supported range: −50 to 80 °C, relative humidity above 0% and at most 100%, and absolute pressure above the saturation vapour pressure.
  • Air is a well-mixed equilibrium mixture at the entered absolute pressure. RH must be above zero to report a finite dew point.
  • Chart curves use the entered pressure and stop where the saturated air state is outside the method range.

Worked examples

These original training examples illustrate the method for North American Technician Excellence Certification (NATE). Use the matching “Load example” button above to explore a variation; example values are not equipment settings or prescribed criteria.

1. Worked example

Read a service air state before deciding whether a comfort complaint concerns temperature, moisture or both. Compare the dry-bulb reading with humidity ratio rather than treating relative humidity as a fixed water content.

Dry-bulb temperature
25 °C
Relative humidity
60 %
Absolute atmospheric pressure
101.325 kPa
  1. Vapour pressure = 0.6 × saturation pressure at 25 °C.
  2. Humidity ratio = 0.011895048534430516 kg water/kg dry air.
  3. Enthalpy = 55.45263614146174 kJ/kg dry air.
  • Dew point: 16.70113 °C
  • Wet bulb: 19.47105 °C
  • Humidity ratio: 11.89505 g/kg dry air
  • Enthalpy: 55.45264 kJ/kg dry air

2. Comparison example

Compare a different supplied condition using the same method. For Technical Conquer, the important check is that the input meaning, units and method assumptions still match the problem.

Dry-bulb temperature
30 °C
Relative humidity
50 %
Absolute atmospheric pressure
101.325 kPa
  1. Vapour pressure = 0.5 × saturation pressure at 30 °C.
  2. Humidity ratio = 0.01331020383863019 kg water/kg dry air.
  3. Enthalpy = 64.21152917460967 kJ/kg dry air.
  • Dew point: 18.44664 °C
  • Wet bulb: 22.00524 °C
  • Humidity ratio: 13.3102 g/kg dry air
  • Enthalpy: 64.21153 kJ/kg dry air

Check your understanding

1. Which relationship is used?

Water vapour pressure = RH × saturation pressure; W = 0.621945 pv/(p−pv). Wet bulb and dew point use standard psychrometric relationships.

2. Which assumption should you check first?

Supported range: −50 to 80 °C, relative humidity above 0% and at most 100%, and absolute pressure above the saturation vapour pressure.

3. How should you verify a different unit system?

Convert every input to the displayed calculation units first. Equivalent physical inputs must give equivalent results; a unit label alone does not convert a number.

Continue with the matching exam topic